
POWER FACTOR EXPLAINED
Most electrical equipment creates an inductive load on the
supply. This inductive load requires a magnetic field to operate,
and when this magnetic field is created, the current will
lag the voltage, i.e. the current will not be in phase with
the voltage. Power Factor Correction compensates for the lagging
current by applying a leading current, reducing
the power factor to close to unity.
What is Power Factor Correction?
The power factor of a supply can be expressed as the cosine
of the angle between Apparent Power and Active Power (cos
ø). The diagrams below show the relationship between
active, reactive and apparent power before and after PFC.
|
Before |
After |
|
|
- Inductive kVAr lags the Active Power by 90°
- Apparent Power is the vector sum of Active Power
and lagging Inductive kVAr
- Power Factor is the cosine of angle ø
|
- Capacitive kVAr now leads the Active Power by 90°
- Apparent Power is the vector sum of Active Power
+ lagging Inductive kVAr + leading Capacitive kVAr
|
|
|
|
 |
|
|
|
|
|
As angle ø is reduced, cos ø tends to 1 (unity
power factor). Both apparent power (kVA) and total reactive
power (kVAr) are significantly reduced.
Flattening the Hill
A good analogy is to envisage a person running along a surface.
The gradient of the surface will influence the effort required.
When the running surface is flat, then the angle ø
between the horizontal and the slope is 0°. As cos 0°
= 1, the runner achieves 100% efficiency, i.e. power factor
= 1 and 100% of the energy burned is being used to run along
the surface. However, if the running surface is steep, say
at 25° to the horizontal, only 90% of the energy burned
is being used to run as cos 25° = 0.9, i.e. power factor
= 0.9. Therefore an extra 10% of energy is required. In laymans
terms, PFC reduces the slope.
|